5.3 Switch settings on chain hoist lifting application
The chain hoist lifting application is activated with switch group S10. The switches must be set according to the
descriptions in the following section.
5.3.1 S10 -2 Chain hoist lifting application
The switch S10 – 2 activates the chain hoist lifting application.
Switch S10- 2 Chain hoist lifting application
0 The chain hoist lifting application is not active.
1 The chain hoist lifting application is active.
Note: The setting shall be used for lifting applications only.
5.3.2 S6 U/f curve settings on chain hoist lifting application
Switch S6 U/f curve settings
-1 -2 -3 Zero Freq Volt [%] U/f Mid Volt [%]
1 1 1 8.5 16
The intermediate point is 5.5 % of the motor’s nominal frequency.